INPUT TECHNICAL DATA Input rated voltage 1-2x 230-400-500 Vac Input voltage AC 187…550 Vac Input voltage DC 270…725 Vdc Frequency 47…63 Hz Current consumption 1.1 A (230 Vac) / 0.55 A (400 Vac) Inrush peak current 20 A Power factor > 0.65 External protection on AC line MT: C-6 A / Fuse: T-4 A OUTPUT TECHNICAL DATA Output voltage range 24 Vdc ±1% Output adjustable range 24…27.5 Vdc Continuous current 5 A Overload limiting 7.5 A for >30 s Short circuit peak current 14 A for 0.4 s Ripple @ nominal ratings 100 mVpp Hold up time 20 ms (230 Vac) / 80 ms (400 Vac) Status indication LED ''DC OK'' / LED ''Alarm'' Alarm contact dry contact, max. 1A Parallel connection possible Redundant parallel connection possible with external ORing diode GENERAL TECHNICAL DATA Efficiency 87% (230 Vac) / 87% (400 Vac) Dissipated power 18 W (230 Vac) / 18 W (400 Vac) Operating temperature range –20…+60°C (derating -3 W >45°C) Input / output isolation 3 KVac / 60 s (SELV output) Input / ground isolation 1.5 kVac / 60 s Output / ground isolation 0.5 kVac / 60 s Standard / approvals EN 60950-1 EMC Standard EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 Overvoltage category / pollution degree II / 2 Protection degree IP 20 Connection terminal 2.5 mm² / 2.5 mm² Housing material aluminium Dimensions (LxHxD) 40x130x115 mm Approximate weight 600 g Mounting information vertical on a rail, 10 mm from adjacent components